Honeywell MC Toolkit Hand Held Communicator
Product Details:
- Rated Voltage 24-240VAC Volt (V)
- Supply Voltage 24-240VAC Volt (v)
- Click to View more
Honeywell MC Toolkit Hand Held Communicator Price And Quantity
- 3000.00 - 7000.00 INR/Unit
- 1 Unit
- 3000 INR/Unit
Honeywell MC Toolkit Hand Held Communicator Product Specifications
- 24-240VAC Volt (V)
- 24-240VAC Volt (v)
Honeywell MC Toolkit Hand Held Communicator Trade Information
- 10 Unit Per Day
- 1 Week
Product Description
Product Details :
Brand | Honeywell |
Model Number | MCT404 |
Weight | Including Battery Weight Approx. 1060 grams (2.3 pounds) |
Operating Temperature | -10 to +50 deg C (+14 to +122 deg F) |
Storage Temperature | -20 to +60 deg C (-4 to +140 deg F) |
PDA | MCT404 - Based on Intermec 70 Series PDA |
Interfaces | USB - Full Speed 2.0 Client ; IrDA, Wi-Fi, Bluetooth |
Dimensions | H8.85 x W3.36 x D2.28 inch,(H225.3 x W85.3 x D57.8mm) |
Operating Humidity | 10 to 90% RH (Check with ECOM) |
Protection Grade | IP65 |
Processor | OMAP Multi Core Processor 1 GHZ |
Memory | 512MB RAM |
Storage | 1GB Flash Memory,Customer accessible microSD slot for removable memory cards up to 32 GB. |
Display | 3.5" VGA Transmissive TFT-LCD touch screen |
Resolution | 640x480 pixels |
Features :
- Configures any Honeywell DE device: SmartLine ST 3000, ST 800, ST 700 Pressure and STT 3000 Temperature Transmitters.
- IrDA port enables IrDA Applications to interface with other IrDA standard devices including: Honeywell ISA100 Wireless devices, UDA 2182
- Analyzers and UDC Controllers
- Configures any HART device with a published
- HART Device Descriptions (DD), regardless of device manufacturer.
- Industrial grade ruggedness with WP IP65 enclosure
- Memory Expandable through industrial grade SD card up to 32GB for data storage
- 480*640 High resolution backlight display with ambient light sensor
- Numeric keypad with large buttons for easy operation or Alpha numeric key pads for convenience like mobile phone and ease of texting
- Supports Wi-Fi for rapid data exchange WLAN: 802.11 a/b/g/n
- Supports easy downloading of any new vendor's DD files via a PC connection.
- Intuitive graphical user interface provides simple navigation and device configuration.
- Available in Intrinsically-safe as well as Non
Intrinsically-safe versions:
- Ruggedized version Environmentally hardened with no approvals.
- Zone 1 approvals: Intrinsically-safe version, available with FM Class I, Div 1/Zone 1 approvals, ATEX and IECEx Zone 1 approvals.
- Fully supports all HART 5.X, HART6.X and wired HART7.X. Commands and utilizes DD-IDE/SDC 625 technology and "Open" Tools standard.
Benefits :
- Supports transmitter diagnostic and on-line monitoring as well as transmitter calibration.
- Standardizes both HART and DE field instrument configuration with one hand-held device.
- Configuration of common, universal and specific device commands is supported.
- User interface provides detailed explanations and sub-menus during the configuration process for ease of operation for even the casual user.
- Comprehensive Device database of all the on line and offline devices with FDM.
- Ability to Schedule Device calibration.
- FDC 2.X Application allows the user to import the device configuration parameters from FDM (Field Device Manager).
- Supports communication with HART devices when the operator is performing the following functions:
- Initial device configuration
- Starting a method
- Changing a configuration parameter
- Determining the actual "state" or process variable of a particular device
- Activating a device's internal diagnostic functions.
Avoid obsolescence issues when vendors publish new DD files:
- Download new device descriptions from the HART website.
- Acquire the latest DD releases from the manufacture's website including device descriptions not available from HART.
- Honeywell FDC 2.X Application comes with built in DD manager which allows easy addition and deletion of DDs. FDC 2.X also supports
- IEC 61804-3 EDDL Standards.
- Honeywell FDC 2.X Application has the facility to create custom views for easier and quicker access to device information.
- Improved DD selection mechanism enables the following configuration options when the proper DD is missing
- Use Generic DD ;Use previous version of DD or Always prompt the user
Memory :
- 2 GB Industrial grade standard micro SD card. (includes all HART registered device descriptions).
- MC Toolkit software, including FDC 2.X and HART DD files, are loaded on flash memory card. The flash memory card in the MCT404 is removable.